Introduction
THIS OPERATING INSTRUCTION APPLY: | |||||||
Type | Box | Colour | Dimensions | Code | |||
RF4PWM/BDN | Metallic | RAL 7035 | 133 x 133 x 91 | PV RF4PW Z2 BDN | |||
RF4PWM/BDN | Circuit DIN35 | 120 x 126 x 90 | PV RF4PW D2 BDN |
Technical Characteristics | ||||||||
|
DECLARATION OF CONFORMITY | |||||||
This equipment conforms with ecc directive 2014/30/UE (EMC- Electromagnetic Compatibility) and directive 2014/35/UE (LVD – Low Voltage Directive) |
|||||||
GUARANTEE | |||||||
1) The controller is guaranteed for a period of 1 year from the date shown on the inside. 2) The guarantee covers the free replacement or repair of components parts that are defective at origin for manufacturing errors. 3) The guarantee is not valid for damage caused accidentally due to improper use or negligence and in case of alterations or repair carried out by unauthorized persons. Design and specifications could be subjected to change without notice. |
|||||||
Code: MUMRF4PWMBDN | Rev..: 00 | Edit: E. Pedrazzi | Date: 08/19 | Sheet : 2 |
SAFETY INSTRUCTIONS | |||||||
DANGER | Indicates an immediate threatening danger. | ||||||
Non-compliance with this information can result in death or serious personal injuries (invalidity). | |||||||
WARNING | Indicates a possibly dangerous situation. | ||||||
Non-compliance with this information can result in death or serious personal injuries (invalidity). | |||||||
CAUTION | Indicates a possibly dangerous situation. | ||||||
Non-compliance with this information can result in damage to property or .light to medium personal injuries. | |||||||
NOTE | Indicates general notes, useful operator tips and operating recommendations |
DIMENSIONS
GENERAL INSTRUCTIONS | |||
DANGER | Before connect the equipment to the mains socket, make sure that the nameplate data match | ||
those of the mains power supply. Only use this equipment in accordance with the porpouse for which it is designed; i.e. for regolation of the amplitude of an electromagnetic vibrator feeder. Any other use is to considered improper, therefore hazardous. The Manufacturer cannot be held liable for any improper, incorrect or unreasonable use of the equipment, switch it off and do not tamper with it. If repair is needed, please contact the Manufacturer’s Technical Service Centre only, as they use original spare parts. |
|||
Failure to observe the above the recommendations could impair the safety of the equipment. All operations regarding adjustement, measurement and testing when required, must only be carried out by authorized and qualified personnel. The Manufacturer shall accept no liability for damage to persons, animals or objects caused by work on the equipment carried out by unauthorized and unqualifield personnel. Before switching on the equipment, connect the mains voltage, conforming to the current regulation, and the vibratory feeder. |
WARNING | Verifying that the installation has an appropriate ground wiring system. | ||
TURN OFF THE POWER BEFORE OPENING. | |||
NOTE | Before using the appliance it is necessary to read attentively the instructions included in this technical | ||
sheet which provides you information about safety installation, use and maintenance. keep this sheet safely for further information. |
|||
NOTE | NOTE : Don’t use the apparatus in proximity of subject zones to vibrations, or in acid and humid | ||
working environment To memorize last setting, wait for 5 second before switch off the controller. |
DIAGNOSTIC- TROUBLESHOOTING | |||||
WARNING | If vibratory feeder works bad or doesn’t work: | ||||
|
|||||
DISPLAY MESSAGE | |||||
AMPLITUDE | FREQUENCY | ON/OFF | |||
0 . 7. OFF | |||||
TECHNICAL CHARACTERISTICS | |||||
TENSION OF FEEDING: 100/240V 50/60Hz CONSUMPTION: 1.5W max CURRENT MAX VIB.: 5A RMS (fuses 4/5A F 250V 5×20 H 1500A) LOAD MIN.: 50mA RMS REG. MIN/MAX.: 0/100% FREQ. OF REG.: 50Hz +/-12Hz o 100Hz +/-12Hz (DP1) (60Hz +/-12Hz o 120Hz +/-12Hz) AUTOMATIC INPUT: 0/10V – (4/20 mA) Reg.Ampiezza – (Reg. 0/10VFrequenza a richiesta) INPUT SENSOR: NPN/PNP (DELAY 0/10 sec.) DEGREE OF PROTECTION: IP65 IN BOX (VERSION DIN35 IP20) DEGREE OF POLLUTION: 2 TEMPERATURE OF STORAGE: -30 °C / + 80 °C TEMPERATURE OF OPERATION: -10 °C / + 50 °C RANGE OF RELATIVE HUMIDITY: 80% TILL TO 31°C INSTALLATION CLASS: II OUTPUT CONNECTOR VIBRATOR: 1-2 vibr. CURRENT LIMITATION: 5 Amp |
OPERATION AND USE | |||||
CONNNECTIONS box version | |||||
Before switching On the unit, connect the plug to the power supply socket, (verifying that the installation has an appropriate ground wiring system) and the socket to the vibratory feeder plug. Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K) on the box. According European Norms EMC the apparatus have a line- filter with leakage current to ground less 1 mA. CONNNECTIONS DIN version Connect the power supply on CONN1, 2-3 (verifying that the installation has an appropriate ground wiring system) and the vibratory feeder to the output connector CONN2, 1-2, Ground CONN1, 1 – CONN2 ,3). Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K-CONN5). According European Norms EMC the apparatus have a line-filter with leakage current to ground less 1 mA. |
|||||
1 | PE | ||||
2 | 3 | ||||
DESCRIPTION OF OPERATION | |||||
The circuit supplies to the vibrator a control signal modulated in impulse width (PWM), which can be regulated both in Amplitude and Frequency. This signal will be compensated as to variations of the line voltage. The protections by fuses are as follows: F1 (6.3 A fast or 4A slow) on the input line, F3 (250 mA) on the ON/OFF input by limiting the current available on the NPN/PNP sensor and/or electro-valve air bolw, F2 (4A) on the vibrator output. The green Led LD2, when On, shows the presence of voltage in the control circuit. It is light Off if are broken fuses F1 and/or F2 and/or F3.The red Led LD1, when On, shows the presence of voltage on the filter capacitors (till 300V with 230V line voltage). The circuit must never be touched when the red Led is On. The yellow Led LD3 when On shows the ON/OFF relay about ON/OFF vibrator (CONN4). |
|||||
MODE OF USE AND ADJUSTMENTS | |||||
The entire control section is galvanically isolated from the power section. When on-switching the circuit. The voltage is supplied to the vibrator, the status relay switches over.
|
CONNECTION NPN/PNP SENSOR
NOTE | ON/OFF Relè | |||||||||||||||||||||||||||||||||||||||||||||||||||
A clean contact is available at the relay ON/OFF, (CONN4) which switches in case of failure with output voltage on the vibrator. This contact is also used for the cascade driving of the various vibrating units in the multiple loading systems. E.V. Blow Air voltage 12Vdc – PNP/NPN sensor voltage 10/30Vdc. |
CROSS REFERENCE RF4 PWM SERIES | |||||||||
RF4 PWM Box Basic |
RF4 PWM Din35 1 pot + no display |
RF4 PWM Box |
RF4PWM Din35 2 pot + display |
RF4PWM Keys Box |
RF4PWM BOX 1 pot + display |
RF4PWM Din35 1 pot + display |
|||
Voltage (50/60 Hz) | 115 o 230V | 115 o 230 | 115 o 230 | 115 o 230 | 115 o 230V | 115 o 230 | 115 o 230 | ||
Amps | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | ||
ON/OFF | ● | ● | ● | ● | ● | ● | ● | ||
Sensor NPN/PNP | ● | ● | ● | ● | ● | ● | ● | ||
0/10V 0/20 mA |
● | ● | ● | ● | – | ● | ● | ||
Amplitude/ Frequency regulation | Pot. Amplitude Trimmer Freq. | Pot. Amplitude Trimmer Freq. | Potentiometer | Potentiometer | Key | Pot. Amplitude Trimmer Freq. | Pot. Amplitude Trimmer Freq. | ||
Output Freq. Hz |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30-130 | 30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
||
Relay ON | ● | ● | ● | ● | ● | ● | ● | ||
Status Relay | ● | ● | ● | ● | ● | ● | ● | ||
EMC – CE | ● | ● | ● | ● | ● | ● | ● | ||
Amplitude Display | – | – | ● | ● | ● | ● | ● | ||
Display Hz | – | – | ● | ● | ● | ● | ● | ||
IP | IP65 | IP20 | IP65 | IP20 | IP65 | IP65 | IP20 | ||
Dimensions Box | 133x133x91 | 120x126x90 | 133x133X91 | 120x126x90 | 133x133x91 | 133x133x91 | 120x126x90 | ||
Photo | 1 | 5 | 3 | 6 | 4 | 2 | 6 |
Related Products:
Introduction
THIS OPERATING INSTRUCTION APPLY: | |||||||
Type | Box | Colour | Dimensions | Code | |||
RF4PWM/BDN | Metallic | RAL 7035 | 133 x 133 x 91 | PV RF4PW Z2 BDN | |||
RF4PWM/BDN | Circuit DIN35 | 120 x 126 x 90 | PV RF4PW D2 BDN |
Technical Characteristics | ||||||||
|
DECLARATION OF CONFORMITY | |||||||
This equipment conforms with ecc directive 2014/30/UE (EMC- Electromagnetic Compatibility) and directive 2014/35/UE (LVD – Low Voltage Directive) |
|||||||
GUARANTEE | |||||||
1) The controller is guaranteed for a period of 1 year from the date shown on the inside. 2) The guarantee covers the free replacement or repair of components parts that are defective at origin for manufacturing errors. 3) The guarantee is not valid for damage caused accidentally due to improper use or negligence and in case of alterations or repair carried out by unauthorized persons. Design and specifications could be subjected to change without notice. |
|||||||
Code: MUMRF4PWMBDN | Rev..: 00 | Edit: E. Pedrazzi | Date: 08/19 | Sheet : 2 |
SAFETY INSTRUCTIONS | |||||||
DANGER | Indicates an immediate threatening danger. | ||||||
Non-compliance with this information can result in death or serious personal injuries (invalidity). | |||||||
WARNING | Indicates a possibly dangerous situation. | ||||||
Non-compliance with this information can result in death or serious personal injuries (invalidity). | |||||||
CAUTION | Indicates a possibly dangerous situation. | ||||||
Non-compliance with this information can result in damage to property or .light to medium personal injuries. | |||||||
NOTE | Indicates general notes, useful operator tips and operating recommendations |
DIMENSIONS
GENERAL INSTRUCTIONS | |||
DANGER | Before connect the equipment to the mains socket, make sure that the nameplate data match | ||
those of the mains power supply. Only use this equipment in accordance with the porpouse for which it is designed; i.e. for regolation of the amplitude of an electromagnetic vibrator feeder. Any other use is to considered improper, therefore hazardous. The Manufacturer cannot be held liable for any improper, incorrect or unreasonable use of the equipment, switch it off and do not tamper with it. If repair is needed, please contact the Manufacturer’s Technical Service Centre only, as they use original spare parts. |
|||
Failure to observe the above the recommendations could impair the safety of the equipment. All operations regarding adjustement, measurement and testing when required, must only be carried out by authorized and qualified personnel. The Manufacturer shall accept no liability for damage to persons, animals or objects caused by work on the equipment carried out by unauthorized and unqualifield personnel. Before switching on the equipment, connect the mains voltage, conforming to the current regulation, and the vibratory feeder. |
WARNING | Verifying that the installation has an appropriate ground wiring system. | ||
TURN OFF THE POWER BEFORE OPENING. | |||
NOTE | Before using the appliance it is necessary to read attentively the instructions included in this technical | ||
sheet which provides you information about safety installation, use and maintenance. keep this sheet safely for further information. |
|||
NOTE | NOTE : Don’t use the apparatus in proximity of subject zones to vibrations, or in acid and humid | ||
working environment To memorize last setting, wait for 5 second before switch off the controller. |
DIAGNOSTIC- TROUBLESHOOTING | |||||
WARNING | If vibratory feeder works bad or doesn’t work: | ||||
Check electric wires. Swicht OFF voltage and to check the fuses and, this case, to check current MAX (ampere) in the vibrator. Check regulations min/max. With input voltage Led Green is ON- with Led Green Is OFF check the fuse F1. 5 Amp output current limitation: the vibrator stops, the display blocks, reduce the amplitude, switch off and check the vibrator. |
|||||
DISPLAY MESSAGE | |||||
AMPLITUDE | FREQUENCY | ON/OFF | |||
0 . 7. OFF | |||||
TECHNICAL CHARACTERISTICS | |||||
TENSION OF FEEDING: 100/240V 50/60Hz CONSUMPTION: 1.5W max CURRENT MAX VIB.: 5A RMS (fuses 4/5A F 250V 5×20 H 1500A) LOAD MIN.: 50mA RMS REG. MIN/MAX.: 0/100% FREQ. OF REG.: 50Hz +/-12Hz o 100Hz +/-12Hz (DP1) (60Hz +/-12Hz o 120Hz +/-12Hz) AUTOMATIC INPUT: 0/10V – (4/20 mA) Reg.Ampiezza – (Reg. 0/10VFrequenza a richiesta) INPUT SENSOR: NPN/PNP (DELAY 0/10 sec.) DEGREE OF PROTECTION: IP65 IN BOX (VERSION DIN35 IP20) DEGREE OF POLLUTION: 2 TEMPERATURE OF STORAGE: -30 °C / + 80 °C TEMPERATURE OF OPERATION: -10 °C / + 50 °C RANGE OF RELATIVE HUMIDITY: 80% TILL TO 31°C INSTALLATION CLASS: II OUTPUT CONNECTOR VIBRATOR: 1-2 vibr. CURRENT LIMITATION: 5 Amp |
OPERATION AND USE | |||||
CONNNECTIONS box version | |||||
Before switching On the unit, connect the plug to the power supply socket, (verifying that the installation has an appropriate ground wiring system) and the socket to the vibratory feeder plug. Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K) on the box. According European Norms EMC the apparatus have a line- filter with leakage current to ground less 1 mA. CONNNECTIONS DIN version Connect the power supply on CONN1, 2-3 (verifying that the installation has an appropriate ground wiring system) and the vibratory feeder to the output connector CONN2, 1-2, Ground CONN1, 1 – CONN2 ,3). Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K-CONN5). According European Norms EMC the apparatus have a line-filter with leakage current to ground less 1 mA. |
|||||
1 | PE | ||||
2 | 3 | ||||
DESCRIPTION OF OPERATION | |||||
The circuit supplies to the vibrator a control signal modulated in impulse width (PWM), which can be regulated both in Amplitude and Frequency. This signal will be compensated as to variations of the line voltage. The protections by fuses are as follows: F1 (6.3 A fast or 4A slow) on the input line, F3 (250 mA) on the ON/OFF input by limiting the current available on the NPN/PNP sensor and/or electro-valve air bolw, F2 (4A) on the vibrator output. The green Led LD2, when On, shows the presence of voltage in the control circuit. It is light Off if are broken fuses F1 and/or F2 and/or F3.The red Led LD1, when On, shows the presence of voltage on the filter capacitors (till 300V with 230V line voltage). The circuit must never be touched when the red Led is On. The yellow Led LD3 when On shows the ON/OFF relay about ON/OFF vibrator (CONN4). |
|||||
MODE OF USE AND ADJUSTMENTS | |||||
The entire control section is galvanically isolated from the power section. When on-switching the circuit. The voltage is supplied to the vibrator, the status relay switches over. Therefore, the following steps can be carried out: Set delay time at the start of the feeder with the TR3 trimmer (0/10 sec) or the delay at the stop of the feeder with the TR2 trimmer (0 / 10sec). Block and restart the feeder with an external control from both a free contact voltage and a sensor NPN or PNP or from a 0 / 24V output by inserting or not the delays mentioned above (see detail Connector 3). With DP1 you can select the straight or negated logic of the ON / OFF signal coming from the sensor or from contact connected to CONN3 (see CONN3 connections). Adjust the start ramp with TR5 (0/3 sec.). Adjust with TR4 max amplitude on the vibrator – adjustment with TR6 min Amp on the vibrator. Automatically adjust the amplitude with 0-10V (4-20 mA) signal by entering CONN7 – setting AUT with DP2. Select the adjustable frequency range with DP1: F1 = 50Hz +/- 12Hz (3000 vib per min. – 3600 vib per min.), F2 = 100Hz +/- 12Hz (6000 vib per min. – 7200 vib per min). Overload: electronic current limitation at 5 Amps. |
CONNECTION NPN/PNP SENSOR
NOTE | ON/OFF Relè | |||||||||||||||||||||||||||||||||||||||||||||||||||
A clean contact is available at the relay ON/OFF, (CONN4) which switches in case of failure with output voltage on the vibrator. This contact is also used for the cascade driving of the various vibrating units in the multiple loading systems. E.V. Blow Air voltage 12Vdc – PNP/NPN sensor voltage 10/30Vdc. |
CROSS REFERENCE RF4 PWM SERIES | |||||||||
RF4 PWM Box Basic |
RF4 PWM Din35 1 pot + no display |
RF4 PWM Box |
RF4PWM Din35 2 pot + display |
RF4PWM Keys Box |
RF4PWM BOX 1 pot + display |
RF4PWM Din35 1 pot + display |
|||
Voltage (50/60 Hz) | 115 o 230V | 115 o 230 | 115 o 230 | 115 o 230 | 115 o 230V | 115 o 230 | 115 o 230 | ||
Amps | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | ||
ON/OFF | ● | ● | ● | ● | ● | ● | ● | ||
Sensor NPN/PNP | ● | ● | ● | ● | ● | ● | ● | ||
0/10V 0/20 mA |
● | ● | ● | ● | – | ● | ● | ||
Amplitude/ Frequency regulation | Pot. Amplitude Trimmer Freq. | Pot. Amplitude Trimmer Freq. | Potentiometer | Potentiometer | Key | Pot. Amplitude Trimmer Freq. | Pot. Amplitude Trimmer Freq. | ||
Output Freq. Hz |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30-130 | 30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
||
Relay ON | ● | ● | ● | ● | ● | ● | ● | ||
Status Relay | ● | ● | ● | ● | ● | ● | ● | ||
EMC – CE | ● | ● | ● | ● | ● | ● | ● | ||
Amplitude Display | – | – | ● | ● | ● | ● | ● | ||
Display Hz | – | – | ● | ● | ● | ● | ● | ||
IP | IP65 | IP20 | IP65 | IP20 | IP65 | IP65 | IP20 | ||
Dimensions Box | 133x133x91 | 120x126x90 | 133x133X91 | 120x126x90 | 133x133x91 | 133x133x91 | 120x126x90 | ||
Photo | 1 | 5 | 3 | 6 | 4 | 2 | 6 |
Related Products:
Introduction
THIS OPERATING INSTRUCTION APPLY: | |||||||
Type | Box | Colour | Dimensions | Code | |||
RF4PWM/BDN | Metallic | RAL 7035 | 133 x 133 x 91 | PV RF4PW Z2 BDN | |||
RF4PWM/BDN | Circuit DIN35 | 120 x 126 x 90 | PV RF4PW D2 BDN |
Technical Characteristics | ||||||||
|
DECLARATION OF CONFORMITY | |||||||
This equipment conforms with ecc directive 2014/30/UE (EMC- Electromagnetic Compatibility) and directive 2014/35/UE (LVD – Low Voltage Directive) |
|||||||
GUARANTEE | |||||||
1) The controller is guaranteed for a period of 1 year from the date shown on the inside. 2) The guarantee covers the free replacement or repair of components parts that are defective at origin for manufacturing errors. 3) The guarantee is not valid for damage caused accidentally due to improper use or negligence and in case of alterations or repair carried out by unauthorized persons. Design and specifications could be subjected to change without notice. |
|||||||
Code: MUMRF4PWMBDN | Rev..: 00 | Edit: E. Pedrazzi | Date: 08/19 | Sheet : 2 |
SAFETY INSTRUCTIONS | |||||||
DANGER | Indicates an immediate threatening danger. | ||||||
Non-compliance with this information can result in death or serious personal injuries (invalidity). | |||||||
WARNING | Indicates a possibly dangerous situation. | ||||||
Non-compliance with this information can result in death or serious personal injuries (invalidity). | |||||||
CAUTION | Indicates a possibly dangerous situation. | ||||||
Non-compliance with this information can result in damage to property or .light to medium personal injuries. | |||||||
NOTE | Indicates general notes, useful operator tips and operating recommendations |
DIMENSIONS
GENERAL INSTRUCTIONS | |||
DANGER | Before connect the equipment to the mains socket, make sure that the nameplate data match | ||
those of the mains power supply. Only use this equipment in accordance with the porpouse for which it is designed; i.e. for regolation of the amplitude of an electromagnetic vibrator feeder. Any other use is to considered improper, therefore hazardous. The Manufacturer cannot be held liable for any improper, incorrect or unreasonable use of the equipment, switch it off and do not tamper with it. If repair is needed, please contact the Manufacturer’s Technical Service Centre only, as they use original spare parts. |
|||
Failure to observe the above the recommendations could impair the safety of the equipment. All operations regarding adjustement, measurement and testing when required, must only be carried out by authorized and qualified personnel. The Manufacturer shall accept no liability for damage to persons, animals or objects caused by work on the equipment carried out by unauthorized and unqualifield personnel. Before switching on the equipment, connect the mains voltage, conforming to the current regulation, and the vibratory feeder. |
WARNING | Verifying that the installation has an appropriate ground wiring system. | ||
TURN OFF THE POWER BEFORE OPENING. | |||
NOTE | Before using the appliance it is necessary to read attentively the instructions included in this technical | ||
sheet which provides you information about safety installation, use and maintenance. keep this sheet safely for further information. |
|||
NOTE | NOTE : Don’t use the apparatus in proximity of subject zones to vibrations, or in acid and humid | ||
working environment To memorize last setting, wait for 5 second before switch off the controller. |
DIAGNOSTIC- TROUBLESHOOTING | |||||
WARNING | If vibratory feeder works bad or doesn’t work: | ||||
Check electric wires. Swicht OFF voltage and to check the fuses and, this case, to check current MAX (ampere) in the vibrator. Check regulations min/max. With input voltage Led Green is ON- with Led Green Is OFF check the fuse F1. 5 Amp output current limitation: the vibrator stops, the display blocks, reduce the amplitude, switch off and check the vibrator. |
|||||
DISPLAY MESSAGE | |||||
AMPLITUDE | FREQUENCY | ON/OFF | |||
0 . 7. OFF | |||||
TECHNICAL CHARACTERISTICS | |||||
TENSION OF FEEDING: 100/240V 50/60Hz CONSUMPTION: 1.5W max CURRENT MAX VIB.: 5A RMS (fuses 4/5A F 250V 5×20 H 1500A) LOAD MIN.: 50mA RMS REG. MIN/MAX.: 0/100% FREQ. OF REG.: 50Hz +/-12Hz o 100Hz +/-12Hz (DP1) (60Hz +/-12Hz o 120Hz +/-12Hz) AUTOMATIC INPUT: 0/10V – (4/20 mA) Reg.Ampiezza – (Reg. 0/10VFrequenza a richiesta) INPUT SENSOR: NPN/PNP (DELAY 0/10 sec.) DEGREE OF PROTECTION: IP65 IN BOX (VERSION DIN35 IP20) DEGREE OF POLLUTION: 2 TEMPERATURE OF STORAGE: -30 °C / + 80 °C TEMPERATURE OF OPERATION: -10 °C / + 50 °C RANGE OF RELATIVE HUMIDITY: 80% TILL TO 31°C INSTALLATION CLASS: II OUTPUT CONNECTOR VIBRATOR: 1-2 vibr. CURRENT LIMITATION: 5 Amp |
OPERATION AND USE | |||||
CONNNECTIONS box version | |||||
Before switching On the unit, connect the plug to the power supply socket, (verifying that the installation has an appropriate ground wiring system) and the socket to the vibratory feeder plug. Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K) on the box. According European Norms EMC the apparatus have a line- filter with leakage current to ground less 1 mA. CONNNECTIONS DIN version Connect the power supply on CONN1, 2-3 (verifying that the installation has an appropriate ground wiring system) and the vibratory feeder to the output connector CONN2, 1-2, Ground CONN1, 1 – CONN2 ,3). Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K-CONN5). According European Norms EMC the apparatus have a line-filter with leakage current to ground less 1 mA. |
|||||
1 | PE | ||||
2 | 3 | ||||
DESCRIPTION OF OPERATION | |||||
The circuit supplies to the vibrator a control signal modulated in impulse width (PWM), which can be regulated both in Amplitude and Frequency. This signal will be compensated as to variations of the line voltage. The protections by fuses are as follows: F1 (6.3 A fast or 4A slow) on the input line, F3 (250 mA) on the ON/OFF input by limiting the current available on the NPN/PNP sensor and/or electro-valve air bolw, F2 (4A) on the vibrator output. The green Led LD2, when On, shows the presence of voltage in the control circuit. It is light Off if are broken fuses F1 and/or F2 and/or F3.The red Led LD1, when On, shows the presence of voltage on the filter capacitors (till 300V with 230V line voltage). The circuit must never be touched when the red Led is On. The yellow Led LD3 when On shows the ON/OFF relay about ON/OFF vibrator (CONN4). |
|||||
MODE OF USE AND ADJUSTMENTS | |||||
The entire control section is galvanically isolated from the power section. When on-switching the circuit. The voltage is supplied to the vibrator, the status relay switches over. Therefore, the following steps can be carried out: Set delay time at the start of the feeder with the TR3 trimmer (0/10 sec) or the delay at the stop of the feeder with the TR2 trimmer (0 / 10sec). Block and restart the feeder with an external control from both a free contact voltage and a sensor NPN or PNP or from a 0 / 24V output by inserting or not the delays mentioned above (see detail Connector 3). With DP1 you can select the straight or negated logic of the ON / OFF signal coming from the sensor or from contact connected to CONN3 (see CONN3 connections). Adjust the start ramp with TR5 (0/3 sec.). Adjust with TR4 max amplitude on the vibrator – adjustment with TR6 min Amp on the vibrator. Automatically adjust the amplitude with 0-10V (4-20 mA) signal by entering CONN7 – setting AUT with DP2. Select the adjustable frequency range with DP1: F1 = 50Hz +/- 12Hz (3000 vib per min. – 3600 vib per min.), F2 = 100Hz +/- 12Hz (6000 vib per min. – 7200 vib per min). Overload: electronic current limitation at 5 Amps. |
CONNECTION NPN/PNP SENSOR
NOTE | ON/OFF Relè | |||||||||||||||||||||||||||||||||||||||||||||||||||
A clean contact is available at the relay ON/OFF, (CONN4) which switches in case of failure with output voltage on the vibrator. This contact is also used for the cascade driving of the various vibrating units in the multiple loading systems. E.V. Blow Air voltage 12Vdc – PNP/NPN sensor voltage 10/30Vdc. |
CROSS REFERENCE RF4 PWM SERIES | |||||||||
RF4 PWM Box Basic |
RF4 PWM Din35 1 pot + no display |
RF4 PWM Box |
RF4PWM Din35 2 pot + display |
RF4PWM Keys Box |
RF4PWM BOX 1 pot + display |
RF4PWM Din35 1 pot + display |
|||
Voltage (50/60 Hz) | 115 o 230V | 115 o 230 | 115 o 230 | 115 o 230 | 115 o 230V | 115 o 230 | 115 o 230 | ||
Amps | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | 4/5 | ||
ON/OFF | ● | ● | ● | ● | ● | ● | ● | ||
Sensor NPN/PNP | ● | ● | ● | ● | ● | ● | ● | ||
0/10V 0/20 mA |
● | ● | ● | ● | – | ● | ● | ||
Amplitude/ Frequency regulation | Pot. Amplitude Trimmer Freq. | Pot. Amplitude Trimmer Freq. | Potentiometer | Potentiometer | Key | Pot. Amplitude Trimmer Freq. | Pot. Amplitude Trimmer Freq. | ||
Output Freq. Hz |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
30-130 | 30/80 – 80/130 50-100 +/-12 |
30/80 – 80/130 50-100 +/-12 |
||
Relay ON | ● | ● | ● | ● | ● | ● | ● | ||
Status Relay | ● | ● | ● | ● | ● | ● | ● | ||
EMC – CE | ● | ● | ● | ● | ● | ● | ● | ||
Amplitude Display | – | – | ● | ● | ● | ● | ● | ||
Display Hz | – | – | ● | ● | ● | ● | ● | ||
IP | IP65 | IP20 | IP65 | IP20 | IP65 | IP65 | IP20 | ||
Dimensions Box | 133x133x91 | 120x126x90 | 133x133X91 | 120x126x90 | 133x133x91 | 133x133x91 | 120x126x90 | ||
Photo | 1 | 5 | 3 | 6 | 4 | 2 | 6 |