Frequency controller RF4PWM/BDN

Introduction

Belt Maintenance ToolsBelt Maintenance Tools

 

THIS OPERATING INSTRUCTION APPLY:
Type Box Colour Dimensions Code
RF4PWM/BDN Metallic RAL 7035 133 x 133 x 91 PV RF4PW Z2 BDN
RF4PWM/BDN Circuit DIN35 120 x 126 x 90 PV RF4PW D2 BDN

Technical Characteristics

  • Power supply 100 / 240V 50 / 60Hz: same model for markets 115V-230V 50 / 60Hz no problem if the power supply is at 50 or 60Hz
  • Fixed frequency: 50Hz-100Hz (3000 -6000Vib per min) -60Hz 120Hz (3600-7200Vib per min)
  • Multifrequency: 50Hz/60Hz +/- 12Hz, 100Hz/120Hz +/- 12Hz (from trimmer). This allows not to change the feeders if the input frequency is different from the vibrator frequency
  • Amplitude adjustment with remote signal 0/1
  • Frequency regulation with remote signal 0/10V (on request
  • Minimum and maximum output adjustment, for better vibration range.
  • Electronic limitation of the maximum current to 5 Amps to protect the controller and the coil of the vibrator.
  • Protection of the electronic stages (input – output – auxiliary) with 3 fast fuses.
  • Input for PNP or NPN sensor with 2 adjustable ON / OFF delays
  • Status relay to be used for cascade systems
  • Double enable logic with +24 signal or free contact voltags
  • Adjustable starting ramp
  • Amplitude-Frequency Display
  • Sine-wave current output for maximum vibrator performance and silence.

DECLARATION OF CONFORMITY
This equipment conforms with ecc directive 2014/30/UE (EMC- Electromagnetic Compatibility)
and directive 2014/35/UE (LVD – Low Voltage Directive)
GUARANTEE
1) The controller is guaranteed for a period of 1 year from the date shown on the inside.
2) The guarantee covers the free replacement or repair of components parts that are defective at origin for manufacturing errors.
3) The guarantee is not valid for damage caused accidentally due to improper use or negligence and in case of alterations or repair carried out by unauthorized persons.
Design and specifications could be subjected to change without notice.
Code: MUMRF4PWMBDN Rev..: 00 Edit: E. Pedrazzi Date: 08/19 Sheet : 2

SAFETY INSTRUCTIONS
DANGER Indicates an immediate threatening danger.
Non-compliance with this information can result in death or serious personal injuries (invalidity).
WARNING Indicates a possibly dangerous situation.
Non-compliance with this information can result in death or serious personal injuries (invalidity).
CAUTION Indicates a possibly dangerous situation.
Non-compliance with this information can result in damage to property or .light to medium personal injuries.
NOTE Indicates general notes, useful operator tips and operating recommendations

 

DIMENSIONS

GENERAL INSTRUCTIONS
DANGER Before connect the equipment to the mains socket, make sure that the nameplate data match
those of the mains power supply.
Only use this equipment in accordance with the porpouse for which it is designed; i.e. for regolation of the amplitude of an electromagnetic vibrator feeder. Any other use is to considered improper, therefore hazardous.
The Manufacturer cannot be held liable for any improper, incorrect or unreasonable use of the equipment, switch it off and do not tamper with it. If repair is needed, please contact the Manufacturer’s Technical Service Centre only, as they use original spare parts.
Failure to observe the above the recommendations could impair the safety of the equipment.
All operations regarding adjustement, measurement and testing when required, must only be
carried out by authorized and qualified personnel.
The Manufacturer shall accept no liability for damage to persons, animals or objects caused by work on the equipment carried out by unauthorized and unqualifield personnel.
Before switching on the equipment, connect the mains voltage, conforming to the current regulation, and the vibratory feeder.

WARNING Verifying that the installation has an appropriate ground wiring system.
TURN OFF THE POWER BEFORE OPENING.
NOTE Before using the appliance it is necessary to read attentively the instructions included in this technical
sheet which provides you information about safety installation, use and maintenance. keep this sheet
safely for further information.
NOTE NOTE : Don’t use the apparatus in proximity of subject zones to vibrations, or in acid and humid
working environment
To memorize last setting, wait for 5 second before switch off the controller.

DIAGNOSTIC- TROUBLESHOOTING
WARNING If vibratory feeder works bad or doesn’t work:
  • Check electric wires.
  •  Swicht OFF voltage and to check the fuses and, this case, to check current MAX (ampere) in
  •  the vibrator.
  •  Check regulations min/max.
  •  With input voltage Led Green is ON- with Led Green
  •  Is OFF check the fuse F1.
  •  5 Amp output current limitation: the vibrator stops, the display blocks, reduce the amplitude, switch off and check the vibrator.
DISPLAY MESSAGE
AMPLITUDE FREQUENCY ON/OFF
0 . 7. OFF
TECHNICAL CHARACTERISTICS
TENSION OF FEEDING: 100/240V 50/60Hz
CONSUMPTION: 1.5W max
CURRENT MAX VIB.: 5A RMS (fuses 4/5A F 250V 5×20 H 1500A)
LOAD MIN.: 50mA RMS
REG. MIN/MAX.: 0/100%
FREQ. OF REG.: 50Hz +/-12Hz o 100Hz +/-12Hz (DP1) (60Hz +/-12Hz o 120Hz +/-12Hz)
AUTOMATIC INPUT: 0/10V – (4/20 mA) Reg.Ampiezza – (Reg. 0/10VFrequenza a richiesta)
INPUT SENSOR: NPN/PNP (DELAY 0/10 sec.)
DEGREE OF PROTECTION: IP65 IN BOX (VERSION DIN35 IP20)
DEGREE OF POLLUTION: 2
TEMPERATURE OF STORAGE: -30 °C / + 80 °C TEMPERATURE OF OPERATION: -10 °C / + 50 °C RANGE OF RELATIVE HUMIDITY: 80% TILL TO 31°C INSTALLATION CLASS: II
OUTPUT CONNECTOR VIBRATOR: 1-2 vibr.
CURRENT LIMITATION: 5 Amp
OPERATION AND USE
CONNNECTIONS box version
Before switching On the unit, connect the plug to the power supply socket, (verifying that the installation has an appropriate ground wiring system) and the socket to the vibratory feeder plug. Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K) on the box. According European Norms EMC the apparatus have a line- filter with leakage current to ground less 1 mA.
CONNNECTIONS DIN version
Connect the power supply on CONN1, 2-3 (verifying that the installation has an appropriate ground wiring system) and the vibratory feeder to the output connector CONN2, 1-2, Ground CONN1, 1 – CONN2 ,3).
Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust
Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K-CONN5). According European Norms EMC the apparatus have a line-filter with leakage current to ground less 1 mA.
1 PE
2 3
DESCRIPTION OF OPERATION
The circuit supplies to the vibrator a control signal modulated in impulse width (PWM), which can be regulated both in Amplitude and Frequency. This signal will be compensated as to variations of the line voltage. The protections by fuses are as follows: F1 (6.3 A fast or 4A slow) on the input line, F3 (250 mA) on the ON/OFF input by limiting the current available on the NPN/PNP sensor and/or electro-valve air bolw, F2 (4A) on the vibrator output.
The green Led LD2, when On, shows the presence of voltage in the control circuit. It is light Off if are broken fuses F1 and/or F2 and/or F3.The red Led LD1, when On, shows the presence of voltage on the filter capacitors (till 300V with 230V line voltage). The circuit must never be touched when the red Led is On. The yellow Led LD3 when On shows the ON/OFF relay about ON/OFF vibrator (CONN4).
MODE OF USE AND ADJUSTMENTS

The entire control section is galvanically isolated from the power section. When on-switching the circuit. The voltage is supplied to the vibrator, the status relay switches over.
Therefore, the following steps can be carried out:

  • Set delay time at the start of the feeder with the TR3 trimmer (0/10 sec) or the delay at the stop of the feeder with the TR2 trimmer (0 / 10sec).
  • Block and restart the feeder with an external control from both a free contact voltage and a sensor NPN or PNP or from a 0 / 24V output by inserting or not the delays mentioned above (see detail Connector 3).
  • With DP1 you can select the straight or negated logic of the ON / OFF signal coming from the sensor or from contact connected to CONN3 (see CONN3 connections).
  •  Adjust the start ramp with TR5 (0/3 sec.).
  •  Adjust with TR4 max amplitude on the vibrator – adjustment with TR6 min Amp on the vibrator.
  •  Automatically adjust the amplitude with 0-10V (4-20 mA) signal by entering CONN7 – setting AUT with DP2.
  •  Select the adjustable frequency range with DP1: F1 = 50Hz +/- 12Hz (3000 vib per min. – 3600 vib per min.), F2 = 100Hz +/- 12Hz (6000 vib per min. – 7200 vib per min).
  •  Overload: electronic current limitation at 5 Amps.

CONNECTION NPN/PNP SENSOR

NOTE ON/OFF Relè
A clean contact is available at the relay ON/OFF, (CONN4) which switches in case of failure with output voltage on the vibrator.
This contact is also used for the cascade driving of the various vibrating units in the multiple loading systems.
E.V. Blow Air voltage 12Vdc – PNP/NPN sensor voltage 10/30Vdc.

 

CROSS REFERENCE RF4 PWM SERIES
RF4 PWM
Box Basic
RF4 PWM Din35
1 pot + no display
RF4 PWM
Box
RF4PWM Din35
2 pot + display
RF4PWM
Keys Box
RF4PWM BOX
1 pot + display
RF4PWM Din35
1 pot + display
Voltage (50/60 Hz) 115 o 230V 115 o 230 115 o 230 115 o 230 115 o 230V 115 o 230 115 o 230
Amps 4/5 4/5 4/5 4/5 4/5 4/5 4/5
ON/OFF
Sensor NPN/PNP
0/10V
0/20 mA
Amplitude/ Frequency regulation Pot. Amplitude Trimmer Freq. Pot. Amplitude Trimmer Freq. Potentiometer Potentiometer Key Pot. Amplitude Trimmer Freq. Pot. Amplitude Trimmer Freq.
Output Freq.
Hz
30/80 – 80/130
50-100 +/-12
30/80 – 80/130
50-100 +/-12
30/80 – 80/130
50-100 +/-12
30/80 – 80/130
50-100 +/-12
30-130 30/80 – 80/130
50-100 +/-12
30/80 – 80/130
50-100 +/-12
Relay ON
Status Relay
EMC – CE
Amplitude Display
Display Hz
IP IP65 IP20 IP65 IP20 IP65 IP65 IP20
Dimensions Box 133x133x91 120x126x90 133x133X91 120x126x90 133x133x91 133x133x91 120x126x90
Photo 1 5 3 6 4 2 6

 

Related Products:

Request A Quote

    Our Products

    Home » Products »  Frequency controller RF4PWM/BDN

    Frequency controller RF4PWM/BDN

     

    Introduction

    Belt Maintenance ToolsBelt Maintenance Tools

     

    THIS OPERATING INSTRUCTION APPLY:
    Type Box Colour Dimensions Code
    RF4PWM/BDN Metallic RAL 7035 133 x 133 x 91 PV RF4PW Z2 BDN
    RF4PWM/BDN Circuit DIN35 120 x 126 x 90 PV RF4PW D2 BDN

    Technical Characteristics

    • Power supply 100 / 240V 50 / 60Hz: same model for markets 115V-230V 50 / 60Hz no problem if the power supply is at 50 or 60Hz
    • Fixed frequency: 50Hz-100Hz (3000 -6000Vib per min) -60Hz 120Hz (3600-7200Vib per min)
    • Multifrequency: 50Hz/60Hz +/- 12Hz, 100Hz/120Hz +/- 12Hz (from trimmer). This allows not to change the feeders if the input frequency is different from the vibrator frequency
    • Amplitude adjustment with remote signal 0/1
    • Frequency regulation with remote signal 0/10V (on request
    • Minimum and maximum output adjustment, for better vibration range.
    • Electronic limitation of the maximum current to 5 Amps to protect the controller and the coil of the vibrator.
    • Protection of the electronic stages (input – output – auxiliary) with 3 fast fuses.
    • Input for PNP or NPN sensor with 2 adjustable ON / OFF delays
    • Status relay to be used for cascade systems
    • Double enable logic with +24 signal or free contact voltags
    • Adjustable starting ramp
    • Amplitude-Frequency Display
    • Sine-wave current output for maximum vibrator performance and silence.

    DECLARATION OF CONFORMITY
    This equipment conforms with ecc directive 2014/30/UE (EMC- Electromagnetic Compatibility)
    and directive 2014/35/UE (LVD – Low Voltage Directive)
    GUARANTEE
    1) The controller is guaranteed for a period of 1 year from the date shown on the inside.
    2) The guarantee covers the free replacement or repair of components parts that are defective at origin for manufacturing errors.
    3) The guarantee is not valid for damage caused accidentally due to improper use or negligence and in case of alterations or repair carried out by unauthorized persons.
    Design and specifications could be subjected to change without notice.
    Code: MUMRF4PWMBDN Rev..: 00 Edit: E. Pedrazzi Date: 08/19 Sheet : 2

    SAFETY INSTRUCTIONS
    DANGER Indicates an immediate threatening danger.
    Non-compliance with this information can result in death or serious personal injuries (invalidity).
    WARNING Indicates a possibly dangerous situation.
    Non-compliance with this information can result in death or serious personal injuries (invalidity).
    CAUTION Indicates a possibly dangerous situation.
    Non-compliance with this information can result in damage to property or .light to medium personal injuries.
    NOTE Indicates general notes, useful operator tips and operating recommendations

     

    DIMENSIONS

    GENERAL INSTRUCTIONS
    DANGER Before connect the equipment to the mains socket, make sure that the nameplate data match
    those of the mains power supply.
    Only use this equipment in accordance with the porpouse for which it is designed; i.e. for regolation of the amplitude of an electromagnetic vibrator feeder. Any other use is to considered improper, therefore hazardous.
    The Manufacturer cannot be held liable for any improper, incorrect or unreasonable use of the equipment, switch it off and do not tamper with it. If repair is needed, please contact the Manufacturer’s Technical Service Centre only, as they use original spare parts.
    Failure to observe the above the recommendations could impair the safety of the equipment.
    All operations regarding adjustement, measurement and testing when required, must only be
    carried out by authorized and qualified personnel.
    The Manufacturer shall accept no liability for damage to persons, animals or objects caused by work on the equipment carried out by unauthorized and unqualifield personnel.
    Before switching on the equipment, connect the mains voltage, conforming to the current regulation, and the vibratory feeder.

    WARNING Verifying that the installation has an appropriate ground wiring system.
    TURN OFF THE POWER BEFORE OPENING.
    NOTE Before using the appliance it is necessary to read attentively the instructions included in this technical
    sheet which provides you information about safety installation, use and maintenance. keep this sheet
    safely for further information.
    NOTE NOTE : Don’t use the apparatus in proximity of subject zones to vibrations, or in acid and humid
    working environment
    To memorize last setting, wait for 5 second before switch off the controller.

    DIAGNOSTIC- TROUBLESHOOTING
    WARNING If vibratory feeder works bad or doesn’t work:
    Check electric wires.
    Swicht OFF voltage and to check the fuses and, this case, to check current MAX (ampere) in
    the vibrator.
    Check regulations min/max.
    With input voltage Led Green is ON- with Led Green
    Is OFF check the fuse F1.
    5 Amp output current limitation: the vibrator stops, the display blocks, reduce the amplitude, switch off and check the vibrator.
    DISPLAY MESSAGE
    AMPLITUDE FREQUENCY ON/OFF
    0 . 7. OFF
    TECHNICAL CHARACTERISTICS
    TENSION OF FEEDING: 100/240V 50/60Hz
    CONSUMPTION: 1.5W max
    CURRENT MAX VIB.: 5A RMS (fuses 4/5A F 250V 5×20 H 1500A)
    LOAD MIN.: 50mA RMS
    REG. MIN/MAX.: 0/100%
    FREQ. OF REG.: 50Hz +/-12Hz o 100Hz +/-12Hz (DP1) (60Hz +/-12Hz o 120Hz +/-12Hz)
    AUTOMATIC INPUT: 0/10V – (4/20 mA) Reg.Ampiezza – (Reg. 0/10VFrequenza a richiesta)
    INPUT SENSOR: NPN/PNP (DELAY 0/10 sec.)
    DEGREE OF PROTECTION: IP65 IN BOX (VERSION DIN35 IP20)
    DEGREE OF POLLUTION: 2
    TEMPERATURE OF STORAGE: -30 °C / + 80 °C TEMPERATURE OF OPERATION: -10 °C / + 50 °C RANGE OF RELATIVE HUMIDITY: 80% TILL TO 31°C INSTALLATION CLASS: II
    OUTPUT CONNECTOR VIBRATOR: 1-2 vibr.
    CURRENT LIMITATION: 5 Amp

    Belt Maintenance Tools
    Belt Maintenance Tools

    OPERATION AND USE
    CONNNECTIONS box version
    Before switching On the unit, connect the plug to the power supply socket, (verifying that the installation has an appropriate ground wiring system) and the socket to the vibratory feeder plug. Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K) on the box. According European Norms EMC the apparatus have a line- filter with leakage current to ground less 1 mA.
    CONNNECTIONS DIN version
    Connect the power supply on CONN1, 2-3 (verifying that the installation has an appropriate ground wiring system) and the vibratory feeder to the output connector CONN2, 1-2, Ground CONN1, 1 – CONN2 ,3).
    Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust
    Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K-CONN5). According European Norms EMC the apparatus have a line-filter with leakage current to ground less 1 mA.
    1 PE
    2 3
    DESCRIPTION OF OPERATION
    The circuit supplies to the vibrator a control signal modulated in impulse width (PWM), which can be regulated both in Amplitude and Frequency. This signal will be compensated as to variations of the line voltage. The protections by fuses are as follows: F1 (6.3 A fast or 4A slow) on the input line, F3 (250 mA) on the ON/OFF input by limiting the current available on the NPN/PNP sensor and/or electro-valve air bolw, F2 (4A) on the vibrator output.
    The green Led LD2, when On, shows the presence of voltage in the control circuit. It is light Off if are broken fuses F1 and/or F2 and/or F3.The red Led LD1, when On, shows the presence of voltage on the filter capacitors (till 300V with 230V line voltage). The circuit must never be touched when the red Led is On. The yellow Led LD3 when On shows the ON/OFF relay about ON/OFF vibrator (CONN4).
    MODE OF USE AND ADJUSTMENTS
    The entire control section is galvanically isolated from the power section. When on-switching the circuit. The voltage is supplied to the vibrator, the status relay switches over.
    Therefore, the following steps can be carried out:
    Set delay time at the start of the feeder with the TR3 trimmer (0/10 sec) or the delay at the stop of the feeder with the TR2 trimmer (0 / 10sec).
    Block and restart the feeder with an external control from both a free contact voltage and a sensor NPN or PNP or from a 0 / 24V output by inserting or not the delays mentioned above (see detail Connector 3).
    With DP1 you can select the straight or negated logic of the ON / OFF signal coming from the sensor or from contact connected to CONN3 (see CONN3 connections).
    Adjust the start ramp with TR5 (0/3 sec.).
    Adjust with TR4 max amplitude on the vibrator – adjustment with TR6 min Amp on the vibrator.
    Automatically adjust the amplitude with 0-10V (4-20 mA) signal by entering CONN7 – setting AUT with DP2.
    Select the adjustable frequency range with DP1: F1 = 50Hz +/- 12Hz (3000 vib per min. – 3600 vib per min.), F2 = 100Hz +/- 12Hz (6000 vib per min. – 7200 vib per min).
    Overload: electronic current limitation at 5 Amps.

    CONNECTION NPN/PNP SENSOR

    NOTE ON/OFF Relè
    A clean contact is available at the relay ON/OFF, (CONN4) which switches in case of failure with output voltage on the vibrator.
    This contact is also used for the cascade driving of the various vibrating units in the multiple loading systems.
    E.V. Blow Air voltage 12Vdc – PNP/NPN sensor voltage 10/30Vdc.

     

    CROSS REFERENCE RF4 PWM SERIES
    RF4 PWM
    Box Basic
    RF4 PWM Din35
    1 pot + no display
    RF4 PWM
    Box
    RF4PWM Din35
    2 pot + display
    RF4PWM
    Keys Box
    RF4PWM BOX
    1 pot + display
    RF4PWM Din35
    1 pot + display
    Voltage (50/60 Hz) 115 o 230V 115 o 230 115 o 230 115 o 230 115 o 230V 115 o 230 115 o 230
    Amps 4/5 4/5 4/5 4/5 4/5 4/5 4/5
    ON/OFF
    Sensor NPN/PNP
    0/10V
    0/20 mA
    Amplitude/ Frequency regulation Pot. Amplitude Trimmer Freq. Pot. Amplitude Trimmer Freq. Potentiometer Potentiometer Key Pot. Amplitude Trimmer Freq. Pot. Amplitude Trimmer Freq.
    Output Freq.
    Hz
    30/80 – 80/130
    50-100 +/-12
    30/80 – 80/130
    50-100 +/-12
    30/80 – 80/130
    50-100 +/-12
    30/80 – 80/130
    50-100 +/-12
    30-130 30/80 – 80/130
    50-100 +/-12
    30/80 – 80/130
    50-100 +/-12
    Relay ON
    Status Relay
    EMC – CE
    Amplitude Display
    Display Hz
    IP IP65 IP20 IP65 IP20 IP65 IP65 IP20
    Dimensions Box 133x133x91 120x126x90 133x133X91 120x126x90 133x133x91 133x133x91 120x126x90
    Photo 1 5 3 6 4 2 6

     

    Related Products:

    Request A Quote

      Our Products

      Introduction

      Belt Maintenance ToolsBelt Maintenance Tools

       

      THIS OPERATING INSTRUCTION APPLY:
      Type Box Colour Dimensions Code
      RF4PWM/BDN Metallic RAL 7035 133 x 133 x 91 PV RF4PW Z2 BDN
      RF4PWM/BDN Circuit DIN35 120 x 126 x 90 PV RF4PW D2 BDN

      Technical Characteristics

      • Power supply 100 / 240V 50 / 60Hz: same model for markets 115V-230V 50 / 60Hz no problem if the power supply is at 50 or 60Hz
      • Fixed frequency: 50Hz-100Hz (3000 -6000Vib per min) -60Hz 120Hz (3600-7200Vib per min)
      • Multifrequency: 50Hz/60Hz +/- 12Hz, 100Hz/120Hz +/- 12Hz (from trimmer). This allows not to change the feeders if the input frequency is different from the vibrator frequency
      • Amplitude adjustment with remote signal 0/1
      • Frequency regulation with remote signal 0/10V (on request
      • Minimum and maximum output adjustment, for better vibration range.
      • Electronic limitation of the maximum current to 5 Amps to protect the controller and the coil of the vibrator.
      • Protection of the electronic stages (input – output – auxiliary) with 3 fast fuses.
      • Input for PNP or NPN sensor with 2 adjustable ON / OFF delays
      • Status relay to be used for cascade systems
      • Double enable logic with +24 signal or free contact voltags
      • Adjustable starting ramp
      • Amplitude-Frequency Display
      • Sine-wave current output for maximum vibrator performance and silence.

      DECLARATION OF CONFORMITY
      This equipment conforms with ecc directive 2014/30/UE (EMC- Electromagnetic Compatibility)
      and directive 2014/35/UE (LVD – Low Voltage Directive)
      GUARANTEE
      1) The controller is guaranteed for a period of 1 year from the date shown on the inside.
      2) The guarantee covers the free replacement or repair of components parts that are defective at origin for manufacturing errors.
      3) The guarantee is not valid for damage caused accidentally due to improper use or negligence and in case of alterations or repair carried out by unauthorized persons.
      Design and specifications could be subjected to change without notice.
      Code: MUMRF4PWMBDN Rev..: 00 Edit: E. Pedrazzi Date: 08/19 Sheet : 2

      SAFETY INSTRUCTIONS
      DANGER Indicates an immediate threatening danger.
      Non-compliance with this information can result in death or serious personal injuries (invalidity).
      WARNING Indicates a possibly dangerous situation.
      Non-compliance with this information can result in death or serious personal injuries (invalidity).
      CAUTION Indicates a possibly dangerous situation.
      Non-compliance with this information can result in damage to property or .light to medium personal injuries.
      NOTE Indicates general notes, useful operator tips and operating recommendations

       

      DIMENSIONS

      GENERAL INSTRUCTIONS
      DANGER Before connect the equipment to the mains socket, make sure that the nameplate data match
      those of the mains power supply.
      Only use this equipment in accordance with the porpouse for which it is designed; i.e. for regolation of the amplitude of an electromagnetic vibrator feeder. Any other use is to considered improper, therefore hazardous.
      The Manufacturer cannot be held liable for any improper, incorrect or unreasonable use of the equipment, switch it off and do not tamper with it. If repair is needed, please contact the Manufacturer’s Technical Service Centre only, as they use original spare parts.
      Failure to observe the above the recommendations could impair the safety of the equipment.
      All operations regarding adjustement, measurement and testing when required, must only be
      carried out by authorized and qualified personnel.
      The Manufacturer shall accept no liability for damage to persons, animals or objects caused by work on the equipment carried out by unauthorized and unqualifield personnel.
      Before switching on the equipment, connect the mains voltage, conforming to the current regulation, and the vibratory feeder.

      WARNING Verifying that the installation has an appropriate ground wiring system.
      TURN OFF THE POWER BEFORE OPENING.
      NOTE Before using the appliance it is necessary to read attentively the instructions included in this technical
      sheet which provides you information about safety installation, use and maintenance. keep this sheet
      safely for further information.
      NOTE NOTE : Don’t use the apparatus in proximity of subject zones to vibrations, or in acid and humid
      working environment
      To memorize last setting, wait for 5 second before switch off the controller.

      DIAGNOSTIC- TROUBLESHOOTING
      WARNING If vibratory feeder works bad or doesn’t work:
      Check electric wires.
      Swicht OFF voltage and to check the fuses and, this case, to check current MAX (ampere) in
      the vibrator.
      Check regulations min/max.
      With input voltage Led Green is ON- with Led Green
      Is OFF check the fuse F1.
      5 Amp output current limitation: the vibrator stops, the display blocks, reduce the amplitude, switch off and check the vibrator.
      DISPLAY MESSAGE
      AMPLITUDE FREQUENCY ON/OFF
      0 . 7. OFF
      TECHNICAL CHARACTERISTICS
      TENSION OF FEEDING: 100/240V 50/60Hz
      CONSUMPTION: 1.5W max
      CURRENT MAX VIB.: 5A RMS (fuses 4/5A F 250V 5×20 H 1500A)
      LOAD MIN.: 50mA RMS
      REG. MIN/MAX.: 0/100%
      FREQ. OF REG.: 50Hz +/-12Hz o 100Hz +/-12Hz (DP1) (60Hz +/-12Hz o 120Hz +/-12Hz)
      AUTOMATIC INPUT: 0/10V – (4/20 mA) Reg.Ampiezza – (Reg. 0/10VFrequenza a richiesta)
      INPUT SENSOR: NPN/PNP (DELAY 0/10 sec.)
      DEGREE OF PROTECTION: IP65 IN BOX (VERSION DIN35 IP20)
      DEGREE OF POLLUTION: 2
      TEMPERATURE OF STORAGE: -30 °C / + 80 °C TEMPERATURE OF OPERATION: -10 °C / + 50 °C RANGE OF RELATIVE HUMIDITY: 80% TILL TO 31°C INSTALLATION CLASS: II
      OUTPUT CONNECTOR VIBRATOR: 1-2 vibr.
      CURRENT LIMITATION: 5 Amp

      Belt Maintenance Tools
      Belt Maintenance Tools

      OPERATION AND USE
      CONNNECTIONS box version
      Before switching On the unit, connect the plug to the power supply socket, (verifying that the installation has an appropriate ground wiring system) and the socket to the vibratory feeder plug. Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K) on the box. According European Norms EMC the apparatus have a line- filter with leakage current to ground less 1 mA.
      CONNNECTIONS DIN version
      Connect the power supply on CONN1, 2-3 (verifying that the installation has an appropriate ground wiring system) and the vibratory feeder to the output connector CONN2, 1-2, Ground CONN1, 1 – CONN2 ,3).
      Before to move pot. Amplitude, you must search the max amplitude with Trimmer Frequency TR1. To adjust
      Amplitude of vibration of the vibratory feeder, turn the adjustement knob (potentiometer 10K-CONN5). According European Norms EMC the apparatus have a line-filter with leakage current to ground less 1 mA.
      1 PE
      2 3
      DESCRIPTION OF OPERATION
      The circuit supplies to the vibrator a control signal modulated in impulse width (PWM), which can be regulated both in Amplitude and Frequency. This signal will be compensated as to variations of the line voltage. The protections by fuses are as follows: F1 (6.3 A fast or 4A slow) on the input line, F3 (250 mA) on the ON/OFF input by limiting the current available on the NPN/PNP sensor and/or electro-valve air bolw, F2 (4A) on the vibrator output.
      The green Led LD2, when On, shows the presence of voltage in the control circuit. It is light Off if are broken fuses F1 and/or F2 and/or F3.The red Led LD1, when On, shows the presence of voltage on the filter capacitors (till 300V with 230V line voltage). The circuit must never be touched when the red Led is On. The yellow Led LD3 when On shows the ON/OFF relay about ON/OFF vibrator (CONN4).
      MODE OF USE AND ADJUSTMENTS
      The entire control section is galvanically isolated from the power section. When on-switching the circuit. The voltage is supplied to the vibrator, the status relay switches over.
      Therefore, the following steps can be carried out:
      Set delay time at the start of the feeder with the TR3 trimmer (0/10 sec) or the delay at the stop of the feeder with the TR2 trimmer (0 / 10sec).
      Block and restart the feeder with an external control from both a free contact voltage and a sensor NPN or PNP or from a 0 / 24V output by inserting or not the delays mentioned above (see detail Connector 3).
      With DP1 you can select the straight or negated logic of the ON / OFF signal coming from the sensor or from contact connected to CONN3 (see CONN3 connections).
      Adjust the start ramp with TR5 (0/3 sec.).
      Adjust with TR4 max amplitude on the vibrator – adjustment with TR6 min Amp on the vibrator.
      Automatically adjust the amplitude with 0-10V (4-20 mA) signal by entering CONN7 – setting AUT with DP2.
      Select the adjustable frequency range with DP1: F1 = 50Hz +/- 12Hz (3000 vib per min. – 3600 vib per min.), F2 = 100Hz +/- 12Hz (6000 vib per min. – 7200 vib per min).
      Overload: electronic current limitation at 5 Amps.

      CONNECTION NPN/PNP SENSOR

      NOTE ON/OFF Relè
      A clean contact is available at the relay ON/OFF, (CONN4) which switches in case of failure with output voltage on the vibrator.
      This contact is also used for the cascade driving of the various vibrating units in the multiple loading systems.
      E.V. Blow Air voltage 12Vdc – PNP/NPN sensor voltage 10/30Vdc.

       

      CROSS REFERENCE RF4 PWM SERIES
      RF4 PWM
      Box Basic
      RF4 PWM Din35
      1 pot + no display
      RF4 PWM
      Box
      RF4PWM Din35
      2 pot + display
      RF4PWM
      Keys Box
      RF4PWM BOX
      1 pot + display
      RF4PWM Din35
      1 pot + display
      Voltage (50/60 Hz) 115 o 230V 115 o 230 115 o 230 115 o 230 115 o 230V 115 o 230 115 o 230
      Amps 4/5 4/5 4/5 4/5 4/5 4/5 4/5
      ON/OFF
      Sensor NPN/PNP
      0/10V
      0/20 mA
      Amplitude/ Frequency regulation Pot. Amplitude Trimmer Freq. Pot. Amplitude Trimmer Freq. Potentiometer Potentiometer Key Pot. Amplitude Trimmer Freq. Pot. Amplitude Trimmer Freq.
      Output Freq.
      Hz
      30/80 – 80/130
      50-100 +/-12
      30/80 – 80/130
      50-100 +/-12
      30/80 – 80/130
      50-100 +/-12
      30/80 – 80/130
      50-100 +/-12
      30-130 30/80 – 80/130
      50-100 +/-12
      30/80 – 80/130
      50-100 +/-12
      Relay ON
      Status Relay
      EMC – CE
      Amplitude Display
      Display Hz
      IP IP65 IP20 IP65 IP20 IP65 IP65 IP20
      Dimensions Box 133x133x91 120x126x90 133x133X91 120x126x90 133x133x91 133x133x91 120x126x90
      Photo 1 5 3 6 4 2 6

       